Microcomputer controlled DC power supply panel CLB-GZDW-2/3/4 aredesigned for various electrical capacity equipment users, of which the systemconfiguration is composed of monitoring module, rectifier module, AC/DCmonitoring module, insulation monitor

share:

Microcomputer controlled DC power supply panel CLB-GZDW-2/3/4 are designed for various electrical capacity equipment users, of which the system configuration is composed of monitoring module, rectifier module, AC/DC monitoring module, insulation monitoring module, the battery inspection module, switch quantity monitoring module, voltage reduction module, power distribution unit, accumulator and cabinets. They have the characteristic of“simple operation, intelligent management and high efficiency and energy saving.”

·               They are applicable for field of electrical power, communication, transportation, chemical industry, metallurgy, military, medical treatment, construction, fire protection, etc. and users terminal. It can be used as operating power supply and control power supply for high voltage switch, relay protection and automatic device


CLB-GZDW-2:
1)
With two - way AC input automatic switching to ensure the normal operation of the system;
2)
The input voltage with wide range, the power grid is well-adapted;
3)
With HZ-JK02B monitoring, LCD screen, Chinese menu, friendly and plentiful interface, the operation of the keys is simple and convenient;
4)
With comprehensive system setup, operation information inquiry and various alarm functions;
5)
With Intelligent battery charge and discharge management and perfect reliable temperature compensation function;
6) expandable battery inspection single set of 110 sections, insulation inspection of 30 ways, switch quantity inspection of 32 ways
7) The system uses multi-level password authority management to limit the operation of unauthorized personnel and ensure the safe and reliable operation of the system ;
8)
The built-in RS232、RS485 communication interface have the function of  operating telemetry, telecontrol, telecommand, tele-regulatingtowards system through background monitoring and remote monitoring to realize unattended operation
9)
Support four communication protocol options of RTU, CDT, MODBUS。

CLB-GZDW-3:
1)
With two - way AC input automatic switching to ensure the normal operation of the system;
2)
The input voltage with wide range, the power grid is well-adapted;
3)
With HZ-JK03 monitoring. The 5.7-inch touch screen display with Chinese interface, man-machine friendly interface and touch operation;
4)
With comprehensive system setup, operation information inquiry and various alarm functions;
5)
With Intelligent battery charge and discharge management and perfect reliable temperature compensation function;
6)
Rectifier module with electric plug, easy and fast daily maintenance;
7)
expandable battery inspection dual sets of 110 sections, insulation inspection of 240 ways, switch quantity inspection of 160 ways, compatible with communication power module, inverter power module and DC conversion module
8) The system uses multi-level password authority management to limit the operation of unauthorized personnel and ensure the safe and reliable operation of the system;
9)
The built-in RS232、RS485 communication interface have the function of  operating telemetry, telecontrol, telecommand, tele-regulatingtowards system through background monitoring and remote monitoring to realize unattended operation
10)
Support four communication protocol options of RTU, CDT, MODBUS。

CLB-GZDW-4:
1)
With two - way AC input automatic switching to ensure the normal operation of the system;
2)
The input voltage with wide range, the power grid is well-adapted;
3)
With HZ-JK04 monitoring, new configuration software, color 7-inch (10.4-inch) LCD display with touch operation, 32-bit true color display, quick refresh speed, intuitive and humanized design which can work for a long time in the state of long light with Perfect human voice alarm system;
4)
With comprehensive system setup, operation information inquiry and various alarm functions;
5)
With Intelligent battery charge and discharge management and perfect reliable temperature compensation function;
6) Rectifier module with electric plug, easy and fast daily maintenance;
7) With Controllable rectifier module up to 26 sets, expandable AC/DC inspection of 2 units, insulation inspection of 240 ways, battery inspection dual sets of 110 sections, switch quantity inspection of 160 ways, compatible with inverter module and DC conversion module.
8) With 32M super storage space, the system has built-in USB interface, with multiple printout system;
9) The system uses multi-level password authority management to limit the operation of unauthorized personnel and ensure the safe and reliable operation of the system;
10) The built-in RS232、RS485 communication interface have the function of  operating telemetry, telecontrol, telecommand, tele-regulatingtowards system through background monitoring and remote monitoring to realize unattended operation
11) Support four communication protocol options of RTU, CDT, MODBUS, IEC

12) According to the needs of users, the system can be customized to add the functions of  image-text display and GPS SMS alarm

Main Parameter:

project

Parameter index

Rated input voltage

380VAC±20%

Rated output voltage

220VDC110VDC

Rated output current

10A15A20A30A40A50A60A70A80A90A

100A120A130A150A180A200A260A300A......

Accumulator capacity

7Ah10Ah20Ah38Ah65Ah100Ah150Ah200Ah300Ah

500Ah600Ah800Ah1000Ah1500Ah2000Ah......

Stabilized voltage precision

≤±0.5%

Stabilized current precision

≤±0.5%

Ripple factor

≤±0.1%

Grid frequency

50Hz±10%

Power factor

≥0.95%(full load output)

Dielectric strength

10MΩ2kVAC No flashover or breakdown for one minute

Working mode

Work for continuous long- term

Cooling mode

Intelligent temperature control type air cooling, efficient natural cooling

Audible noise

≤50dB

Environmental condition:

1) Altitude: not more than 2000 meters ;
2) Environment temperature: -10
~+40℃;
3) Relative humidity:
90(25)
4) Seismic intensity: not more than 8
℃;
5)
Equipment is limited to indoor work with good ventilation;
6) The room should be free of corrode metal and harmful gases that damage insulation

7) Install vertical inclination: not more than 5
℃;
8 The micro-controller for noise resistant: 1000V 1μs pulse for 1 minute
9)
With no strong electromagnetic interference and violent vibration。

System Configuration

Name

Size

Specification

Functional specification

Monitoring module

CLB -JK series

Must be configured

Rectifier module

CLB series

Ac/dc monitoring module

CLB -JZL series

Voltage reduction module

CLB -GL series

Insulation monitoring module

CLB -JY series

optional

Battery inspection module

CLB -XJ series

Switch quantity monitoring module

CLB -JD series

Inverter module

CLB -NB series

DC conversion module

CLB 24S/48S series

The power distribution units

Configure according to user’s requirements

Battery

Cabinet body

2) Monitoring module selection

Name

Type

Specification

Notes

Monitoring module

CLB -JK02

Liquid Crystal Display

CLB -JK03

Touch screen

CLB -JK04

True color graphic touch screen

CLB -JK05T

3) Rectifier module selection

Name

Type

Specification

Functional specification

Notes

Rectifier Module

CLB 22005

220VDC 5A

Independently Display, query and Setting

CLB 11010

110VDC 10A

CLB 22010

220VDC 10A

CLB 11020

110VDC 20A

CLB 22020

220VDC 20A

CLB 11040

110VDC 40A

① Current calculation
  The configuration of the rectifier module is mainly determined by the maximum constant load current and battery charging current C10(battery capacity). The total rated output current of all modules should be greater than or equal to the sum of the maximum constant load current and battery charging current of the system。If N+1 redundancy is to be realized, one more module should be added on the basis of the original number

② The number calculation
The number of rectifier module configuration is calculated according to the following two formulas.Control bus without rectifier module:

4) functional module selection

Name

Type

Specification

Functional specification

Notes

Insulation monitoring module

CLB -JY02B

30 way×4

Please click detailed page

4 in parallel connection

AC/DC monitoring module

CLB -JZL01A

AC 2 way, DC 8 way

Battery inspection module

CLB -XJ01A

22 section ×5

5 in parallel connection

Switch quantity monitoring module

CLB -JD01

32 way ×5

Voltage reduction module

CLB -GL03

20-100A

Inverter module

CLB -NB

1-6KVA

Configure according to user’s requirements

DC conversion module

CLB 24S/48S

24/48VDC

Insulation detector

Please refer to the random instruction for details.

Battery inspection instrument

signal alarm device

Distribution unit section

Name

Type

Size

Functional specification

Notes

AC Circuit Breaker

optional

optional

Ac input on off and overload short circuit protection

Configure according to user’s requirements

Dual Power Switch

Ac input automatic switching and overload short circuit protection

AC Contactor

Ac input is automatically switched

DC Circuit Breaker

Module output, control power bus and closing power source bus output, battery power supply and overload, short circuit protection

Pointer Current Voltmeter

Input/output voltage/current indication

Digital Display Current Voltmeter

Input/output voltage/current display

Fusible Knife Switch

Battery power on and off and circuit protection

Fuse

Battery power on and off, circuit protection and fuse alarm

electric reactor

Suppress harmonics and improve power quality

Lightning arrestor

Protection against lightning overvoltage shock

Overvoltage protector

The protection of over voltage, under voltage and default phase of AC input

Special component

Realize other function

(1) The standard configuration is the input ac second circuit, the output dc control power supply bus under 65 Ah is 3 circuit, the closing power supply bus is 3 circuit, the output dc control bus is 5 circuit and the closing power supply bus is 5 circuit, the current voltmeter is the pointer board meter。
(2) The configuration can be customized according to user’s requirements

6) battery selection

Type selection

Type

DC Voltage

Specification Ah

Functional specification

Lead-acid battery

2V

7-2500Ah

Maintenance-free

12V

7-200Ah

Colloid storage battery

2V

7-2500Ah

Maintenance-free, long service life

12V

7-200Ah

The standard configuration is lead-acid batteries。

quantity configuration

System voltage

Battery voltage

Section number

Functional specification

220VDC

2V

110

Series connection battery sets

12V

18

110VDC

2V

55

12V

9

capacity calculation

 The capacity of the battery is determined by the maximum instantaneous load of the system which are in the state of power failure, and the surplus must be appropriately increased in combination with the actual situation.The system load is divided into constant load (Izc), emergency load (Isg) and impact load (Ihz).The constant load mainly includes the frequently charged relay, signal lamp and other electrical equipment connected to the DC system. The emergency load is the load that must be power supplied by the dc system when the power is cut off due to the loss of ac power in the power substation, mainly for accident lighting.The impact load is mainly the sum of the borne loads of which the short (0.1~ 0.5s) closing impact current and with its DC bus.The maximum instantaneous load is the sum of the above three loads, namely the maximum instantaneous load of the battery Imax=Izc+Isg+Ihz, then the battery capacity =Imax/ battery discharge rate * reserve coefficient (Ah)。

(1) The discharge rate of maintenance-free lead-acid batteries is usually 0.1。
(2) The above calculation method can achieve the continuous discharge for 1 hour of the system which is in the state of power failure

(3)
The remaining battery capacity shall not be less than 25 of the rated capacity to avoid excessive discharge of battery when the battery is closed at the end of discharge。
(4)
Considering the decaying capacity at the end of battery aging, the reserve coefficient of 1.2 is generally chosen。

7) The choice for the cabinet body

model selection guide of cabinet body

type

size

Functional specification

notes

Standard configuration

2200x800x600

With GGD structure, computer gray standard plastic spray, The aluminum alloy frame glass door for the front side, The double door for the back side, the lighting is equipped inside the cabinet,  temperature control automatic ventilation for the top side

Height x width x depth(mm)

2260x800x600

advanced configuration

2200x800x600

With C type structure, computer gray standard plastic spray, The advanced aluminum alloy frame glass door for the front side, The double door for the back side, the lighting is equipped inside the cabinet,  temperature control automatic ventilation for the top side

2260x800x600

The structure, color and specifications can be customized according to users’requirements。

surface counting

System capacity (Ah)

10~50

65~120

150~200

250~350

400~500

600~800

1000

Surface quantity of the cabinet body

Single battery

1

2-3

3-4

4-5

5-6

7-8

9-10

Double battery

2

3-4

4-5

6-7

10-12

12-14

14-17

(1) The configuration surface quantity of the cabinet body depends on the number of modules, feeder circuit number, battery capacity and dc voltage, etc. The above calculation is for reference only。
(2)
The batteries with a capacity above 200Ah can be installed by battery rack

8) please refer to the page link for the instruction of system installation, commissioning, using and breakdown maintenance,
9) please refer to the page link for the instruction of battery installation, using and maintaining